| STANDARD PRODUCT SPECIFICATIONS
AND AVAILABLE OPTIONS |
| Requirement |
Applicability of Requirement |
Design Value
|
| Basic Impulse Levels,
BIL |
Rated voltages for transformer
winding: 1.2kV |
10 kV |
20, 30 kV |
| (specified as a
function of transformer winding voltage) |
Rated voltages for transformer
winding: 2.5kV |
30 kV |
45 kV |
| |
Rated voltages for transformer
winding: 2.5kV |
60 kV |
75 kV |
| |
Rated voltages for transformer
winding: 8.7kV |
75 kV |
95 kV |
| |
Rated voltages for transformer
winding: 15kV |
95 kV |
10 kV |
| |
Rated voltages for transformer
winding: 25kV |
125 kV |
150 kV |
| |
Rated voltages for transformer
winding: 34.5kV |
150 kV |
170 kV |
| Winding Temperature Rise, °C |
For all power ratings and voltage
classes |
80 °C |
115 °C |
| Forced Air Rating |
Transformers rated 150-3750 kVA |
133% |
150% |
| |
Transformers rated greater than 3750
kVA |
133% |
140% |
| Conductor Material |
For all power ratings and voltage
classes |
Copper |
Aluminum |
| Maximum Operating
Ambient Temperature |
Operating ambient temperature range
-40 °C to 30 °C average, with specified maximum |
40 °C max |
50 °C
max |